Fire Curtains

Smoke Curtains — BÖLDT FC-SM

Containing Smoke, Protecting Escape Routes

EN 12101-1TÜV SÜD VERIFIEDGRAVITY FAIL-SAFE
BÖLDT smoke curtain

Overview

Smoke Reservoirs Without Permanent Bulkheads

Engineered to EN 1634-1 / EN 12101-1 · Manufactured in Jaipur

Smoke curtains descend automatically on smoke detection to subdivide large volumes — atriums, malls, warehouses and car parks — into smoke reservoirs, channelling smoke toward smoke and heat exhaust ventilation (SHEV) extract points and keeping escape routes clear of smoke logging for longer. Tested to EN 12101-1 for smoke control curtains and barriers, and deployed using the BÖLDT Fail-Safe Descent mechanism used across the BÖLDT fire curtain range, smoke curtains require no standby power to close on activation or power loss.

How It Works

Forming the reservoir

SHEV extractEscape route kept clearSmoke curtainForms downstand barrierSmoke reservoirChannelled to extract
FIG. 06Smoke control — reservoir & escape routeBÖLDT · Not to scale
  • Concealed head box houses the curtain fabric above the ceiling line until activation
  • On smoke detection, the fabric descends to form a continuous downstand barrier
  • Smoke is channelled within the resulting reservoir toward dedicated extract points
  • Curtains can be configured in linked banks to subdivide a single large volume into multiple reservoirs

Application

Where This Curtain is Specified

Shopping mall and atrium smoke reservoir subdivision, warehouse and logistics facilities with SHEV systems, basement and multi-level car parks, and any large volume where smoke control strategy requires curtain boards that remain concealed during normal use.

Full Specification

FabricSmoke-resistant glass-fibre composite
Head boxConcealed, powder-coated steel
DeploymentAutomatic on smoke detection
Closure mechanismGravity fail-safe
Side guidesSteel channel, full height
Bottom barSteel, weighted
Smoke leakageMinimised per EN 12101-1
FunctionSmoke reservoir / curtain board
Test standardEN 12101-1
CertificationTÜV SÜD verified
Power dependencyNone for closure
ClassificationEN 13501-2

How It Deploys

Gravity fail-safe deployment

01

Standby

Fabric concealed in the head box; opening clear during normal use.

02

Deployment

On alarm or power loss, the curtain descends under gravity along steel guides.

03

Sealed

Weighted bottom bar seats to the floor, forming a continuous fire barrier.

FIG. 01Gravity fail-safe deployment sequenceBÖLDT · Not to scale